Indicate your email address
to receive information concerning
our new services and our offers.


 

ROCKBOARD® RCK
MINERAL WOOL

ISO 9001 : 2000 Certified
 

ROCKBOARD® products are mineral wool fiber insulations made from basalt rock and slag. This combination results in a non-combustible product with a melting point of approximately 2150°F (1177°C), which gives it excellent fire resistance properties. ROCKBOARD® mineral wool is a water repellent yet vapor permeable material.
 

The RCK™ series of products are non-combustible mineral wool insulation boards that are lightweight, water repellent and designed to allow for various application requirements. A major application for the RCK series is pipe and tank wrap, where temperature demands as well as moisture resistance are critical. Low moisture absorption, non-corrosive, chemically inert, CFC and HCFC free product and process.

Technical data //

 
Test Method
Compliance and Performance
RCK 35
RCK 40

RCK 60

ASTM C 612 Mineral Fiber Block and Board Thermal Insulation Type IVA, complies Type IVA, complies Type IVB, complies
 

Fire Performance :

     
CAN4-S114 Test for Non-Combustibility Non-Combustible Non-Combustible Non-Combustible
ASTM E 136 Behavior of Materials at 750°C
(1382°F)
Non-Combustible Non-Combustible Non-Combustible
CAN/ULC S102 Surface Burning Characteristics Flame Spread = 5
Smoke Developed =10
Flame Spread = 5
Smoke Developed =10
Flame Spread = 5
Smoke Devel. =10
ASTM E 84
(UL 723)
Surface Burning Characteristics
Flame Spread = 5
Smoke Developed =5
Flame Spread = 5
Smoke Developed =5
Flame Spread = 5
Smoke Devel. =10
 

Maximum Service Temperature :

     
ASTM C 411 Hot Surface Performance In Compliance with ASTM C612
at 1200°F (650°C)
In Compliance with ASTM C612
at 1200°F (650°C)
In Compliance with ASTM C612 at 1200°F (650°C)
 

Dimensional Stability :

     
ASTM C 356 Linear Shrinkage 0.35 % at 1200°F
(650°C)
0.47% at 1200°F
(650°C)
1.14 % at 1200°F (650°C)
 

Moisture Resistance :

     
ASTM C 1104 Moisture absorption 0.3 % 0.03 % 0.07 %
 

Fungi Resistance :

     
ASTM C 1338 Determination of Fungi Resistance Passed Passed Passed
 

Corrosion Resistance:

     
ASTM C 665 Corrosiveness to Steel Passed Passed Passed
ASTM C 795*** Stainless Steel Stress Corrosion Specification as per Test Methods C871 and C692 :U.S. Nuclear Regulatory Commission, Reg.Guide # 1.36: U.S. Military SpecificationsMIL-I-24244 (all versions including B and C) Conforms Conforms Conforms
 

Thermal Performance :

     
ASTM C 518
(C 177)

R-value/inch at 75°FRSI
value/25.4 mm at 24°C

4.1/hr.ft².F/Btu
0.72 m² K/W
4.1/hr.ft².F/Btu
0.72 m² K/W
4.2/hr.ft².F/Btu
0.74 m² K/W
 

Compressive Strength :

     
ACTM C 165  at 10% 71 psf (3.4 kPa) 90 psf (4.3 kPa) 196 psf (9.4 kPa)
   at 25% 209 psf (10 kPa) 226 psf (10.8 kPa) 547 psf (26.2 kPa)
 

Density :

     
ACTM C 612-00 Actual 3.5 lbs/ft³ (56 kg/m³) 4.0 lbs/ft³ (64 kg/m³) 6.0 lbs/ft³
(96 kg/m³)
*** Provisions for lot testing may be required, consult manufacturer.
Note : ® is a registered trademark.

06-10/rev.0

N.B. The information, details, dimensions and values indicated are to our best knowledge. We recommend testing according to local conditions. The specifications are subject to change without notice.
 
55, Route 116 West, Danville (Quebec) J0A 1A0 Tel.: (819) 839-2793
Fax: (819) 839-2797 • www.industries3r.com



Company  I  News  I  Custom Made Products  I  Contact  I  Site Guide  I  Home  I  Top of page
© Copyright 2008, Industries 3R inc. All rights reserved I 1 819 839-2793


May we help you find a product ?